12–1
SECTION 12
Final Power-Up
••••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Earth Ground Connections
AC Power-Up
Connecting the Backup Battery
Battery Tests
••••••••••••••••••••••••••••••••••••••••••••••••••
Earth Ground Connections
The designated earth ground terminal (25) must be terminated in a good earth ground for
the lightning transient protective devices in this product to be effective. It also must be
grounded to enable the telephone line fault indicator to work properly. The following are
examples of good earth grounds available at most installations:
Metal Cold Water Pipe: Use a noncorrosive metal strap (copper is recommended) firmly
secured to the pipe to which the ground lead is electrically connected and secured.
AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test the
integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such
as the UL Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores.
AC Power-Up
To turn on AC power, perform the following steps:
1. Plug the 1321 or 4300 Transformer into a 24-hour, unswitched 120VAC outlet.
Following power-up, one of the following will be displayed: AC, dI (disabled); BUSY
STANDBY (alpha keypads); or NOT READY (fixed-word keypads). The green POWER
LED (or READY LED on some keypads) should light.
2. After approximately 1 minute, the initial displays will revert to SYSTEM READY for
alpha keypads, or READYENTER CODE for fixed-word keypads (if there are no
faulted zones). This 1-minute delay allows PIRs, etc. to stabilize.
To bypass this delay, press: # + 0.
Connecting the Backup Battery
In the event of an AC power loss, the control panel is supported by a backup, rechargeable
Sealed Lead Acid battery. The minimum battery size recommended is the No. 467 (12V,
4AH) battery. See paragraph titled, Calculating the Battery Size Needed that follows.
The battery is installed in the control cabinet.
The standby battery is automatically tested every 6 hours, beginning 6 hours after exiting
Programming mode. In addition, entry into the Test mode will cause a battery test to be
initiated.
Calculating the Battery Size Needed (based on total current drawn & standby time wanted)
Determine the total device current draw after filling in the Auxiliary Device Current Draw
Worksheet that follows. To this figure add the 100mA that is drawn by the control panel
itself. Then, to determine the battery size needed, use the following formula:
Total Current Drawn
*
x Number of hours standby wanted = Battery Ampere/Hours.
*
Convert mA figure to decimal Amps (see example that follows).
Vista de pagina 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 143 144

Comentarios a estos manuales

Sin comentarios

Bradford White UDS Series manuali

Manuali dei proprietari e guide per l'utente per Riscaldatori e bollitori per acqua Bradford White UDS Series.
We fornisce 1 manuali pdf Bradford White UDS Series per scaricare gratuitamente in base al tipo di documento: Manuale di Servizio






Più prodotti e manuali per Riscaldatori e bollitori per acqua Bradford White

Modelli Tipo di Documento
M4403T Manuale di Servizio   Bradford White M4403T Service manual, 28 pagine
BRADFORD WHITE EVERHOT TG-237I-N(X)A Manuale delle Istruzioni   Bradford White BRADFORD WHITE EVERHOT TG-237I-N(X)A Instruction manual, 68 pagine
POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Guida alla Risoluzione dei Problemi   Bradford White POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Troubleshooting guide, 60 pagine
238-16152-00F Manuale delle Istruzioni   Bradford White 238-16152-00F Instruction manual, 44 pagine
BNTV Manuale Utente   736-B - Bradford White, 6 pagine
E32-50S Manuale di Servizio   Bradford White E32-50S Service manual [en] , 20 pagine
M4TW60T Series Manuale di Servizio   Bradford White M4TW60T Series Service manual, 40 pagine
D-38T-155 Manuale Utente   735-B - Bradford White, 4 pagine
20A Manuale delle Istruzioni   Bradford White 20A Instruction manual, 24 pagine
20A Manuale di Servizio   Bradford White 20A Service manual, 44 pagine
POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Guida alla Risoluzione dei Problemi   Bradford White POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Troubleshooting guide, 60 pagine
238-37281-00R Manuale delle Istruzioni   Bradford White 238-37281-00R Instruction manual, 28 pagine
PDV80S150 Manuale Utente   752-B - Bradford White, 2 pagine
BRADFORD WHITE EVERHOT TG-237I-N(X)A Manuale di Servizio   Bradford White BRADFORD WHITE EVERHOT TG-237I-N(X)A Service manual, 64 pagine
30A Manuale delle Istruzioni   Bradford White 30A Instruction manual, 20 pagine
POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Manuale delle Istruzioni   Bradford White POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Instruction manual, 40 pagine
POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Manuale delle Istruzioni   Bradford White POWERED DIRECT VENT SERIES GAS-FIRED COMMERCIAL WATER HEATER Instruction manual, 55 pagine
BRUTE DELUXE BMT2H Istruzioni per gli Interventi    Bradford White BRUTE DELUXE BMT2H Operating instructions, 44 pagine
500-1825 Guida alla Risoluzione dei Problemi   Bradford White 500-1825 Troubleshooting guide, 28 pagine
12A Manuale delle Istruzioni   Bradford White 12A Instruction manual, 55 pagine